Technical guide
Off-grid operation and grid-forming control: a PCS terminology guide
A manufacturer-authored explanation distinguishes a system's physical operating condition from its voltage- and frequency-control characteristics.
October 2026 technical edition. Operating modes, transfer performance, black start and grid support require model- and system-specific verification; this conceptual guide is not a site design or commissioning procedure.
People working in storage, microgrids and distributed PV frequently encounter the terms 'off-grid' and 'grid-forming'. They are often confused: some assume off-grid operation is the same as grid forming, while others think grid forming is only for backup during an outage. They describe different dimensions, however, and can be combined. Understanding the distinction helps explain PCS grid-connected and islanded operation, weak-grid support and black start. This guide sets out the author's conceptual comparison.
1. The central distinction
Off-grid
Off-grid describes the PCS operating condition: physically disconnected from the main grid and independently supplying local loads.
Grid-forming
Grid-forming describes a control characteristic: the equipment establishes its own voltage and frequency reference rather than depending on the main grid.
In brief
Off-grid describes 'where the equipment operates'; grid-forming describes 'how it operates'. In the author's explanation, stable islanded operation requires grid-forming control, but grid-forming capabilities are not limited to islanded applications.
2. What is off-grid operation?
Definition
Off-grid operation means separation from the public grid. Following a grid fault, outage or deliberate opening of the point-of-common-coupling switch, the PCS no longer connects to the utility grid. In the battery-storage example described here, it uses stored electricity to supply local equipment and loads independently, functioning like a high-power industrial uninterruptible supply.
Operating characteristics
1. No external grid reference: there is no external voltage or frequency signal to follow.
2. Local load variations must be supported: the PCS and battery handle load starts, stops and power changes, increasing requirements for load capability and stability.
3. A dedicated control mode: the guide describes switching to voltage-and-frequency, or V/f, control as the basic grid-forming approach for this operating condition.
Industry scale and revenue models listed in the original guide
Scale: large, centralised megawatt-class storage within the utility-storage sector.
Investors: commonly grid companies and independent storage operators.
Revenue sources: capacity leasing, grid ancillary services and peak-shaving compensation.
A key misconception
The guide contrasts this with a conventional grid-following PCS operating only in PQ control. Such a device behaves as a current source and needs a grid reference; when that reference is removed it blocks and stops rather than independently supplying power.
3. What is grid-forming control?
Definition
Grid-forming, or GFM, is a PCS control approach. Unlike equipment that simply follows the grid, a grid-forming PCS can actively establish an AC voltage and frequency reference without relying on an external reference. It emulates characteristics of a conventional synchronous generator and is important for storage used with weak or islanded grids.
Two operating forms
Confusion often arises from knowing that grid-forming control can support islanded operation without recognising its grid-connected applications.
1. Islanded grid forming: with the external grid disconnected, the PCS establishes the local microgrid and supplies its loads. This is central to the backup and islanded systems discussed in the guide.
2. Grid-connected grid forming: the device remains connected to the main grid but actively contributes voltage support, virtual inertia and damping rather than simply following it. The guide identifies renewable bases and commercial sites with weak grids as relevant applications.
Capabilities highlighted by the author
The author highlights short-circuit support, weak-grid adaptability, resistance to oscillatory instability, black start and grid-connected/islanded transition capabilities as characteristics sought in advanced storage PCS systems.
4. Comparing off-grid operation and grid-forming control
5. Combining the concepts in engineering applications
The guide summarises the two PCS categories as follows.
1. Conventional grid-following PCS in PQ control
Characteristic: current-source behaviour that follows the main grid.
Capability in this comparison: grid-connected energy trading and generation.
Limitation in this comparison: no grid forming or independent islanded supply; loss of the grid reference causes shutdown.
Applications listed: strong-grid areas, straightforward time-of-use arbitrage and stable grid-connected generation, with lower costs.
2. Advanced grid-forming PCS
Characteristic: voltage-source behaviour and autonomous establishment of the electrical reference.
Dual-mode operation
Grid-connected: virtual-synchronous-generator control to support weak grids, stabilise voltage and add inertia.
Islanded: V/f control for local supply, emergency backup and black start.
Applications listed: microgrids, commercial backup, island supply, large renewable-energy bases and weak-grid regions.
Femi Digital Energy develops, manufactures and sells storage and PV products and invests in, builds and operates storage, PV and integrated projects. Its proprietary products include storage systems, PCS, DC–DC converters, static transfer switches, energy-management systems, microgrids and virtual-power-plant systems for integrated energy applications.